Electrical characteristics |
||
Measure Type |
3P3W ACsystem,3P4W ACsystem |
|
Sampling rate |
128 points per cycle |
|
Data refresh rate |
1S |
|
Measure accuracy |
Current |
±0.2%FS |
Voltage |
±0.2%FS |
|
Power |
0.5S |
|
Frequency |
±0.001Hz |
|
Active Energy |
|
|
Reactive Energy |
|
|
DC input |
0.5% FS |
|
DC output |
0.5% FS |
|
Input voltage characteristics |
Measure |
3 *220/380V(Directly input) |
3 * 57.7/100V(PT secondary side) |
||
Allowed overload capability |
1.2 times/continuous |
|
Input resistance |
300KΩ/phase |
|
Input current characteristics |
Measure current |
5A (CT Secondary side)Or 1A (CT Secondary side) |
Allowed Overload capability |
1.2 times/continuous |
|
Input resistance |
<0.1Ω |
|
Binary input |
Working valtage |
15 VDC |
Input |
12KΩ |
|
Isolation |
2KV |
|
Relay Output |
Node type |
Mechanical contact |
Node capability |
220 VAC/5A、30 VDC/5A |
|
4-20mA DC input measurement |
Measure current |
4-20mA |
Allowed capability |
1.2 times/continuous |
|
Input resistance |
10Ω |
|
Isolation |
2KV |
|
0-5V DC input measurement |
Measure |
0-5V |
Allowed capability |
1.2 times/continuous |
|
Input resistance |
12.5KΩ |
|
Isolation |
2KV |
|
4-20mA DC output |
Open-circuit |
15VDC |
Load capability |
≤600Ω |
|
Isolation |
2KV |
|
Power supply |
AC |
85~264 VAC/45-65Hz |
DC |
100~375 VDC |
|
Power consumption |
< 3W |
|
Mechanical performance |
||
weight |
<0.5kg |
|
IP protection Level |
Meter Panel IP52 Meter Host IP30 |
|
Dimension |
Host |
75 X 75 X 113 mm |
Working temperature |
Display screen |
-20~70℃ |
Meter |
-25~70℃ |
|
Storage temperature |
Meter+display screen |
-40~85℃ |
Relative humidity |
5% - 90%RH,No condensation |
|
EMC |
||
Antistatic discharge interference |
IEC 61000-4-2,Level 4 |
|
Anti-fast transient group pulse |
IEC 61000-4-4,Level 4 |
|
Anti-surg |
IEC 61000-4-5,Level 3 |
|
Resistance to power frequency magnetic field |
IEC 61000-4-8,Level 3 |
|
Electrical insulation performance |
||
Insulation resistence |
GB/T13729,>50MΩ |
|
Power frequency withstand |
GB/T13729,AC 3KV 50Hz /1min |
|
Impulse voltage |
GB/T13729,5KV,1.2/50us |
1.Outer Dimension of PMC72S Multifunctional Power Meter as below chart (1):
Chart(1)PMC72S outer dimension and hole size for installation (mm)
2. Insert the PMC72S meter into the hole of 67mm X 67mm,and then fasten the PMC72S meter with the , as below Chart (2)
Back label,as chart (3):
Chart(3) Wiring Terminal and Marker
Terminal signal :
Code |
Name |
Description |
1、2 |
L/+、N/- |
Working power supply input |
3、4 |
RL1+、RL1- |
Relay 1 output |
5、6 |
A+、A- |
AI/AO signal input/output |
7 |
S1 |
Switch 1 input |
8 |
S2 |
Switch 2 input |
9 |
SG |
Switch value input common terminal |
10、11 |
- |
Reserved |
12、13 |
A,B |
RS458 communication port |
14 |
V1 |
A Phase voltage input |
15 |
V2 |
B Phase voltage input |
16 |
V3 |
C Phase voltage input |
17 |
Vn |
Vn (Un) input |
18、19 |
I1+、I1- |
A Phase current input |
20、21 |
I2+,I2- |
B Phase current input |
22、23 |
I3+、I3- |
C Phase current input |
System Wiring Type
When the measuring voltage is less than or equal to 264v (phase) / 456v (line),can be directly connected without external PT. Otherwise, it must be connected with external PT.The meter supports a variety of measurement wiring modes, which are described in the following Chart.
Chart (4) 3 phase/4 line wiring system,No PT,3CT Chart (5) 3 phase/4 line wiringsystem,3PT,3CT
Chart (6) 3 phase/3 line wiring system,No PT,3CT Chart(7)3 phase/3 line wiring system,No PT,2CT
Chart (8) 3 phase/3 line wiring system,2PT,3CT Chart (9) 3 phase/3 line wiring system,2PT,2CT
Note: The fuse in above charts should be rated at 250mA fuse.
PMC72S Guide for selection of power parameter measurement and control instrument
Model specification:PMC72S-①-②-③-④-⑤ |
|
① Model code: |
|
1 |
57.7/100V Rated measurement voltage,5A Rated measurement current。 |
2 |
57.7/100V Rated measurement voltage,1A Rated measurement current。 |
3 |
220/380V Rated measurement voltage,5A Rated measurement current。 |
4 |
220/380V Rated measurement voltage,1A Rated measurement current。 |
② Model code: |
|
1 |
Power supply:85~264 VAC/45-65Hz,100~300 VDC |
③ Model code: |
|
0 |
Without DI |
2 |
2 Channels DI |
④ Model code: |
|
0 |
Without relay output |
1 |
Optional 1 Channel relay output |
⑤ Model code: |
|
ab |
ab is a 2 integer,a means AI01 port optional for AI/AO modules,b means AI02 port optional for AI/AO 0–none 1 -0-5VDCanaloginputmeasure(AI) 2 -4-20mA DC analog input measure(AI) 3 -4-20mA DC analog output(AO)For example:ab=00,Means AI01 port is not equipped with AI/AO module,AI02 port is not equipped with AI/AOmodule ab =01,Means options 0-5V DC analog input measure; |
For example:Order model:PMC72S-3-1-2-1-02
Means PMC72S rated measure 220/380V、5A;working power supply as 85~264 VAC/45-65Hz;optional with 2channels binary input(DI);1channels relay output;1channel 4-20mA DC analog input measure (AI01 port),1 channel 4-20mA DC analog input measure(AI02 port)