Electrical Characteristics |
||
Measure type |
3P3W AC system,3P4W AC system |
|
Sampling Rate |
64 points per cycle | |
Data refresh rate |
1S |
|
Measure accuracy |
Current |
0.2%FS |
Voltage |
0.2%FS |
|
Power |
0.5% |
|
Frequency |
0.05Hz |
|
Active energy |
1.0% |
|
Reactive energy |
2.0% |
|
AI |
0.5% |
|
AO |
0.5% |
|
Input Voltage Characteristics |
Measure Voltage |
3 *220/380V |
3 * 57.7/100V |
||
Allowed overload |
1.2 times / continuous |
|
input resistance |
1.8MΩ |
|
Input current characteristics |
measure current |
5A (CT Secondary side)Or 1A (CT Secondary side) |
Allowed overload |
1.2 times / continuous |
|
input resistance |
< 0.1Ω |
|
Binary input |
Working |
12~24VDC |
input resistance |
12KΩ |
|
isolation voltage |
2KV |
|
Relay output |
Node type |
Mechanical contact |
Node capacity |
220VAC/5A , 30VDC/5A |
|
4-20mA DC input measurement |
measure current |
4-20mA |
Allowed overload |
1.2 times / continuous |
|
input resistance |
10Ω |
|
isolation voltage |
2KV |
|
0-5V DC input measurement |
Measure voltage |
0-5V |
Allowed overload |
1.2 times / continuous |
|
input resistance |
12.5KΩ |
|
isolation voltage |
2KV |
|
4-20mA DC output |
Open circuit voltage |
15VDC |
Load capability |
≤ 600Ω |
|
isolation voltage |
2KV |
|
Power supply |
AC AC |
100~240VAC/45-65Hz |
DC |
100~375VDC |
|
Power consumption |
< 3W |
|
Mechanical performance | ||
weight |
0.5kg |
|
IP Protection Level | Meter Panel IP52,Meter Host IP30 | |
Dimension |
host |
96 X 96 X 72mm |
host + modules |
96 X 96 X 120mm |
|
Working temperature |
display |
-20~70 ℃ |
meter |
-25~70 ℃ |
|
storage temperature |
Meter + Display |
-40~85 ℃ |
Relative humidity |
5% - 90%RH , No condensation |
|
EMC |
||
Anti-static discharge interference |
IEC 61000-4-2, Level 4 |
|
Anti-fast transient group pulse |
IEC 61000-4-4, Level 4 |
|
Anti-surge |
IEC 61000-4-5, Level 3 |
|
Resistance to power frequency magnetic field |
IEC 61000-4-8, Level 3 |
|
Electrical insulation performance | ||
Insulation resistance |
GB/T13729 , > 50MΩ |
|
Power frequency withstand voltage |
GB/T13729 , AC 2KV 50Hz /1min |
|
Impulse voltage |
GB/T13729 , 5KV , 1.2/50us |
Chart (1) outer size
Chart (2) Front side installment show
3、Use the two fastener to fixed into the left/right side of the host, to fixed the PMC200 meter,As chart (3).
Chart (3) Back side of the installment show
4、Use the screw BM2.5X64 fix the AUX module onto the host, as chart (4)
Chart (4) AUX module installment show
Note: must install the fastener before install the AUX module.
Wiring
Terminal and Marker
Code |
Name |
Description |
1、3 |
L/+、N/- |
Working Power supply input |
2、4 |
NC、NC |
Empty |
5、6 |
NC、NC |
Empty |
7、8 |
P2-、P2+ |
Reactive power pulse output,No-power-optocoupler Isolate; |
9、10 |
P1-、P1+ |
Active power pulse output,No-power-optocoupler Isolate; |
11、12 |
B-、A+ |
RS485 Communication Port |
13 |
SHD |
RS485 Shielding layergrounding; |
2、Marker 2 on bottom of Host, as chart (6) as below:
Chart (6) Marker 2
Code |
Name |
Description |
14、16 |
V1、V2 |
Voltage input |
18、20 |
V3、Vn |
|
21、22 |
I1+、I1- |
Current input |
23、24 |
I2+、I2- |
|
25、26 |
I3+、I3- |
|
15、17 |
NC、NC |
Empty |
19 |
NC |
System Wiring Type
When the measuring voltage is less than or equal to 277v (phase) / 480v (line),can be directly connected without external PT. Otherwise, it must be connected with external PT.The meter supports a variety of measurement wiring modes, which are described in the following Chart.
Chart (7) 3 phase/4 line wiring system,No PT,3CT Chart (8) 3 phase/4 line wiring system,3PT,3CT
Chart (9) 3 phase/3 line wiring system,No PT,3CT Chart(10)3 phase/3 line wiring system,No PT,2CT
Chart (11) 3 phase/3 line wiring system,2PT,3CT Chart (12) 3 phase/3 line wiring system,2PT,2CT
Note: The above diagram fuse should be rated at 250mA fuse.
PMC200 Multifunctional Power Meter Selection Guide
Model :PMC200-A-B-C-D-E-F-G |
|
A Rated measuring voltage, current: |
|
1 |
57.7/100V,5A |
2 |
57.7/100V,1A |
3 |
220/380V,5A |
4 |
220/380V,1A |
B Power system frequency |
|
1 |
50Hz |
2 |
60Hz |
C Power Supply |
|
1 |
85~265 VAC/45-65Hz,100~300 VDC |
D Host A slot Expansion module |
|
0 |
No |
1 |
8-channel digital input module |
2 |
6-channel digital input module |
E Host B slot Expansion module |
|
0 |
No |
1 |
4 Relay Output Module |
F Host C slot Expansion module |
|
0 |
No |
1 |
Analog Input / Output Module 1 AI : 4-20mA 1 AI : 0-5V 2 AO : 4-20mA |
G Host D slot Expansion module |
|
0 |
No |
1 |
RS232 Communication module |
2 |
TCP/IP module |
3 |
ProfiBus-DP module |