Electrical Safety Monitoring Instrument

Home > Electrical Safety Monitor...

KNPS304 Intelligent and Safe Power Monitoring Device

Item No.: 00010
The intelligent and safe power monitoring device shall be applied to TT and TN power distribution systems below 0.4kV. Provide efficient data support for safe electricity use, and solve the safety problem of electrical equipment.
Add to Inquiry
Description Technical Parameters Application Network Diagram Installation Wiring
       The intelligent safe power use solution adopts the Internet of Things sensing technology to conduct continuous data tracking and statistical prediction on the main factors that cause electrical fires (such as abnormal cable temperature, voltage, overload and leakage). With the help of big data analysis and mining, it can timely find and troubleshoot the potential safety hazards of electrical lines and electrical equipment, achieve the goal of preventing from "burning", and truly achieve intelligent and safe power use, Promote the construction and harmonious development of smart cities.
       The smart and safe power management platform is based on the big data analysis of the cloud platform and is mainly applied to TT and TN power distribution systems below 0.4kV. It can accurately identify the safety conditions such as electric leakage, short circuit and overload of electrical equipment, and has the functions of positioning and early warning, equipment abnormality diagnosis and accident tracing. Provide reliable data basis for safe electricity use for city managers and owners of electrical equipment, and solve the safety problem of electrical equipment.

      The intelligent power safety monitoring device is a combined electrical fire detector that uses segment LCD display and integrates real-time detection of three current signals, one leakage signal, four temperature signals and audible and visual alarm functions. The design, manufacture and inspection of this detector comply with the national standard GB14287-2014, Part 2 and Part 3. It is stable and reliable in operation and flexible in application.

1. One circuit leakage current monitoring. The leakage current alarm value range is 0.1~9.999A.

2. Four way temperature monitoring. Temperature alarm value range: 45~140 ℃.

3. Zero ground voltage monitoring. Zero ground voltage alarm value range: 0.5~10V.

4. One switch output (relay contact).

5. One circuit reclosing relay.

6. Three phase full power monitoring. Voltage, current, frequency, power, power factor, electric energy. Voltage measurement rating: 220/380. It can be overloaded by 1.5 times. Current measurement rating: 50/100/200. Various specifications of current transformer can be selected (external connection of current transformer).

7. Total harmonic of voltage and current (THD), 2~31th harmonic distortion.

8. 128 * 64 dot matrix LCD display.

9. Operation, mute, alarm and fault indicators.

10. Buzzer alarm.

11. Rail mounted.

12. Working voltage: 85~264VAC, 110~375VDC.

Measure accuracy

Current

0.5%FS

Voltage

0.5%FS

Power

1S

frequency

± 0.01Hz

Active energy

1S

Reactive energy

2S

Temperature

± 2 ℃

Leakage current

±10mA

Neutral ground voltage

0.5%FS

     The smart and safe power management platform is an electrical fire hazard management system based on big data, including smart sensing terminal for power safety, power safety platform, and comprehensive services for electrical fire hazard management.

Installation
Chart(1)KNPS304 outer dimension  for installation (mm),use 35mm DIN rail mounting

Chart(1)
Wiring

Serial No.

Name

Description

32

L/+N/-

Working Power supply input

1

PE

Ground circuit

3334

B-A+

RS485 Communication interface

12

 

Reclosing relay is normally closed

13

 

Common terminal of reclosing relay

14

 

Reclosing relay is normally open

1516

 

Switching value output (alarm output)

1718

T1

A-phase temperature input (regardless of polarity)

1920

T2

B-phase temperature input (regardless of polarity)

2122

T3

C-phase temperature input (regardless of polarity)

2324

T4

N-phase temperature input (regardless of polarity)

3132

I4+I4-

Residual current transformer input (regardless of polarity)

2526

I1+I1-

Phase A current input

2728

I2+I2-

Phase B current input

2930

I3+I3-

Phase C current input

68104

V1V2V3Vn

Voltage input

  Chart(2)


Chart(3)

Note: the temperature sensor is connected to the outlet terminal of the circuit breaker