The intelligent power safety monitoring device is a combined electrical fire detector that uses segment LCD display and integrates real-time detection of three current signals, one leakage signal, four temperature signals and audible and visual alarm functions. The design, manufacture and inspection of this detector comply with the national standard GB14287-2014, Part 2 and Part 3. It is stable and reliable in operation and flexible in application.
1. One circuit leakage current monitoring. The leakage current alarm value range is 0.1~9.999A.
2. Four way temperature monitoring. Temperature alarm value range: 45~140 ℃.
3. Zero ground voltage monitoring. Zero ground voltage alarm value range: 0.5~10V.
4. One switch output (relay contact).
5. One circuit reclosing relay.
6. Three phase full power monitoring. Voltage, current, frequency, power, power factor, electric energy. Voltage measurement rating: 220/380. It can be overloaded by 1.5 times. Current measurement rating: 50/100/200. Various specifications of current transformer can be selected (external connection of current transformer).
7. Total harmonic of voltage and current (THD), 2~31th harmonic distortion.
8. 128 * 64 dot matrix LCD display.
9. Operation, mute, alarm and fault indicators.
10. Buzzer alarm.
11. Rail mounted.
12. Working voltage: 85~264VAC, 110~375VDC.
Measure accuracy |
Current |
0.5%FS |
Voltage |
0.5%FS |
|
Power |
1S |
|
frequency |
± 0.01Hz |
|
Active energy |
1S |
|
Reactive energy |
2S |
|
Temperature |
± 2 ℃ |
|
Leakage current |
±10mA |
|
Neutral ground voltage |
0.5%FS |
The smart and safe power management platform is an electrical fire hazard management system based on big data, including smart sensing terminal for power safety, power safety platform, and comprehensive services for electrical fire hazard management.
Serial No. |
Name |
Description |
3、2 |
L/+、N/- |
Working Power supply input |
1 |
PE |
Ground circuit |
33、34 |
B-、A+ |
RS485 Communication interface |
12 |
|
Reclosing relay is normally closed |
13 |
|
Common terminal of reclosing relay |
14 |
|
Reclosing relay is normally open |
15、16 |
|
Switching value output (alarm output) |
17、18 |
T1 |
A-phase temperature input (regardless of polarity) |
19、20 |
T2 |
B-phase temperature input (regardless of polarity) |
21、22 |
T3 |
C-phase temperature input (regardless of polarity) |
23、24 |
T4 |
N-phase temperature input (regardless of polarity) |
31、32 |
I4+、I4- |
Residual current transformer input (regardless of polarity) |
25、26 |
I1+、I1- |
Phase A current input |
27、28 |
I2+、I2- |
Phase B current input |
29、30 |
I3+、I3- |
Phase C current input |
6、8、10、4 |
V1、V2、V3、Vn |
Voltage input |