Multi function Power Meter

Home > Multi function Power Mete...

Din rail multi tariffs 220/380V modbus power meter

Din rail multi function energy meter with temperature IO, providing the harmonics analyzing and THD monitoring. DTSD63 din rail energy meter is a rail-mounted power monitoring and control instrument, which integrates data acquisition and control functions
Request Quote
Description Product Feartures Main Specifications Ordering Guide
Products Description

Based on the measurement of RMS, the rail-mounted DTSD63 instrument accurately monitors extremely nonlinear loads. It can precisely measure a number of power parameters, such as voltage/current, frequency, power, power factor, energy, and current/voltage harmonics, thanks to advanced grid frequency simultaneous sampling technology.

In contrast to conventional energy meters, the DTSD63 boasts cost-saving features, a small size, ease of deployment, and data collecting and control capabilities. Energy management systems, intelligent buildings, intelligent distribution panels, high and low voltage switchgear, community power distribution, industrial automation, power plant power systems, substation automation, distribution network automation, and other scenarios can all make extensive use of it.

You can learn more about power load conditions, pinpoint times of peak energy use, and implement focused energy-saving strategies with the help of the DTSD63. With the 485 communication interface that our product provides, you can communicate with other smart systems and devices to manage energy more intelligently.

Main Features

Instantaneous true RMS value

Current

each single phase and conjunction, average

Phase voltage/line voltage

each single phase and conjunction, average

Active, reactive, apparent power

each phase and the sum of three phases

Power factor

each phase and the sum of three phases

Frequency

45~65Hz

Maximum/minimum value

Max/min rms current

/

Max/min rms phase voltage

/

Max/min total active, reactive, apparent power

/

Max/min total power factor

/

Max/min frequency

/

Max/min THD I & THD U

/

Demand and peak demand value

Current per phase

current value/peak/month-end peak

Total active, total reactive, total apparent power

current value/peak/month-end peak

Energy

Input/output/total active energy

1 pulse output(multiplexed)

Input/output/total reactive energy

1 pulse output(multiplexed)

Apparent electrical energy

/

Moth-end electrical energy

/

Multi-tariffs

8 billing periods, 4 tariffs can be set

Power quality

Total Harmonic Distortion Rate (THD)

current and voltage

1st-31th harmonic analysis

current and voltage

Voltage crest factor CF and current K coefficient

Event logging

100 SOE event records

Alarm

8 configurable limit alarm channels & 4 configurable logical alarm channels

Communication

RS-485 /MODBUS-RTU, DL/T 645-2007

Display

TFT LCD

Real-time clock

Year, month, day, minute, second

Other

Program online upgrade supported

Optional Features

Digital Input (DI)

4 switching inputs

Digital Output (DO)

1 relay output, which can be set by local limit alarm or controlled remotely

Temperature Sampling Input

1-8 channels digital temperature sensor input

Electrical characteristics

System

3P3W, 3P4W

Measurement accuracy

Current

±0.2%FS

Voltage

±0.2%FS

Power

0.5S

Frequency

45~65Hz,error: ±0.2%

Active energy

0.5S

Reactive energy

2.0S

Temperature

-10℃~+85℃, error: ±0.5℃
-45℃~+125℃, error: ±2.0℃

Voltage input

Measuring voltage

3*220/380V, 3*57.7/100V(3P4W)

3*100V, 3*380V(3P3W)

Current input

Measuring current

3×1(6)A, 3×10(80)A or external CT

Digital input

Operating voltage

5 VDC

Digital output

Node type

Node capacity

Mechanical contacts

220 VAC/5A,30 VDC/5A

Working power supply(three options)

Voltage supply

50~450 VAC/45-65Hz

Auxiliary AC

85~265 VAC/45-65Hz

Auxiliary DC

9~36 VDC

Power consumption

< 3W

Function

Display

Screen

TFT LCD

Resolution

240*320

Communication

Interface

RS485

Protocol

Modbus-RTU, DL/T 645-2007

Baud rate

2400, 4800, 9600, 19200, 38400, 57600

Switching IO

Output

1 relay output, 2A/30VDC or 2A/250VAC (optional)

Input

4 channels dry contact inputs(optional)

Temperature measurement

Channels

0-8 (optional)

Method of measuring

Digital temperature sensor

Pulse output

PPS output

Default to PPS output

Energy pulse output

1 active optocoupler output, 1 reactive optocoupler output

Pulse constant

7200imp/kWh, 400imp/kWh (optional)

Mechanical characteristic

Weight

≤0.5kg

Size

126mm*88.5mm*69.5mm

Operating temperature

-20~70°C

Storage temperature

-25~70°C

Humidity

≤93%RH, non-condensing, no corrosive gases

Altitude

≤2500m

CodeDTSD63-A-B-C-D-E-F

A. Model code: Rated measuring voltage

1

3×57.7/100V

2

3×220/380V

3

3×100V

4

3×380V

B. Model code: Rated measuring current

1

3×1(6)A

2

3×10(80)A

3

External current transformer, current is customized according to customer needs

4

Other models can be customized through transformer connection

5

Direct access to other models for customization

C. Model code: Working power mode

1

Three-phase voltage supply

2

Auxiliary AC power supply mode,

3

Auxiliary DC power supply mode

D. Model code: Switch input

0

No DI

4

4 -way DI

E. Model code: Relay output

0

No relay output

1

Optional 1-way relay output (RL1+, RL1- ports)

F. Model code: Temperature measurement input

0

Without digital temperature sensor

1-8

The number of digital temperature sensors is 4 as standard.