a. Full power parameter measurement, electric energy measurement, up to 31 times voltage and current harmonic analysis;
g. The product can be connected with an open current transformer to realize the construction and transformation of uninterrupted power supply.
The PMC180N-S Three-phase Digital Power Meter is a multi-function power parameter measuring instrument without display operation panel, which can replace a variety of instruments, transformers and other components, and can be installed in different positions in the power distribution system.
The instrument has RS-485 communication interface, optional wireless communication module, can be integrated into a variety of power monitoring systems, and data collection can be conveniently carried out through the supporting management software or other industrial configuration software.
This instrument is a true rms-based measuring instrument that can accurately measure highly nonlinear loads. Advanced grid frequency synchronous sampling technology enables it to accurately measure a variety of power parameters, including voltage / current rms, frequency, active power, reactive power, apparent power, power factor, input / output active energy, total active energy, Input / output reactive power, total reactive power, apparent power, voltage total harmonic distortion (THD) , 1~31 voltage harmonics, current total harmonic distortion (THD) and 1~31 current harmonics, etc. . All measurements, maximum and minimum values, and demand measurements can be viewed remotely using the software.
a.Industrial distribution automation system b.Energy efficiency management system
c.Substation automation system d. Electrical engineering of intelligent building
e.Power plant auxiliary power system f.High and low voltage switchgear
Electrical Characteristics |
||
Measure Type |
3P3W ACsystem,3P4W ACsystem |
|
Sampling Rate |
128 points per cycle |
|
Data refresh rate |
1S |
|
Measure accuracy |
Current |
± 0.2%FS |
Voltage |
± 0.2%FS |
|
Power |
0.5S |
|
Frequency |
± 0.001Hz |
|
Active energy |
0.5S |
|
Reactive energy |
1.0S |
|
DC input (AI) |
0.5% FS |
|
DC output (AO) |
0.5% FS |
|
Input Voltage Characteristics |
Measure |
3 *220/380V ( direct access ) |
3 * 57.7/100V (PT secondary side ) |
||
Allowed overload capability |
1.2 times / continuous |
|
input resistance |
300K Ω / phase |
|
Input current characteristics |
measure current |
5A (CT Secondary side)Or 1A (CT Secondary side) |
Allowed Overload capability |
1.2 times / continuous |
|
input resistance |
< 0.1Ω |
|
Switch input |
Working valtage |
15VDC |
input resistance |
12KΩ |
|
isolation voltage |
2KV |
|
4-20mA DC input measurement |
measure current |
4-20mA |
Allowed Overload capability |
1.2 times / continuous |
|
input resistance |
10Ω |
|
isolation voltage |
2KV |
|
0-5V DC input measurement |
Measure |
0-5V |
Allowed Overload capability |
1.2 times / continuous |
|
input resistance |
12.5KΩ |
|
isolation voltage |
2KV |
|
4-20mA DC output |
Open-circuit |
15VDC |
load capacity |
≤ 600Ω |
|
isolation voltage |
2KV |
|
Power supply |
AC AC |
85~264VAC/45-65Hz |
DC |
100~375VDC |
|
Power consumption |
< 3W |
|
Mechanical performance |
||
weight |
|
|
IP protection class |
Meter Host IP30 |
|
Dimension |
host |
110 X 80 X 75mm |
Operating temperature |
meter |
-25~ |
storage temperature |
meter |
-40~ |
Relative humidity |
5% - 90%RH , no condensation |
|
EMC |
||
Anti-static discharge interference |
IEC 6 |
|
Immunity to fast transient bursts |
IEC 6 |
|
Anti-surge |
IEC 6 |
|
Anti-power frequency magnetic field |
IEC 6 |
Installation
PMC180N 3-phase digital power meter (no indicator) use 35mm DIN rail mounting or use M4 screws.
Fig. (1) Frame size (Unit:mm)
System wiring connection patterns
The power parameter meter can measure directly when the voltage less than or equal to 264V (phase) / 456V (line) and does not need to connect an external PT, otherwise it need to connect via an external PT. The power parameter meter support a variety wiring of measurement modes and as following use the graph of the method (Fig. 2..... Fig.7) to process explanation separately.
Fig. (2) 3 phase/4 line wiring system,No PT,3CT Fig. (3) 3 phase/4 line wiring system,3PT,3CT
Fig. (4) 3 phase/3 line wiring system,No PT,3CT Fig. (5) 3 phase/3 line wiring system,No PT,2CT
Fig. (6) 3 phase/3 line wiring system,2PT,3CT Fig. (7) 3 phase/3 line wiring system,2PT,2CT
Note: The fuse in the above diagrams is recommended at the rated current 250 mA.
Model Specifications: PMC180N-S- ① - ② - ③ - ④ |
|
① Model code: |
|
1 |
57.7/100V rated measuring voltage, |
2 |
57.7/100V rated measuring voltage, |
3 |
220/380V rated measuring voltage, |
4 |
220/380V rated measuring voltage, |
5 |
57.7/100V rated measuring voltage, external current transformer. |
6 |
220/380V rated measuring voltage, external current transformer. |
②Model code: |
|
1 |
Working power: 85~264 VAC/45-65Hz , 100~300 VDC . |
③'s model code: |
|
0 |
No DI |
1 |
1 way DI |
④ Model code: |
|
0 |
none |
1 |
0-5V DC analog input measurement (AI) |
2 |
4-20mA DC analog input measurement (AI) |
3 |
03 - 4-20mA DC analog output (AO) |
* Note: DI and AI/AO ports are multiplexed. If DI is selected, AI/AO cannot be selected; if AI/AO is selected for A1 port, DI cannot be selected.
Example: The ordering model is: PMC180N-S-3-1-1-0
That is, PMC180N-S is rated to measure 220/380V , 5A ; the working power is 85~264 VAC/45-65Hz ; it is equipped with 1 switch input (DI) ; there is no AI/AO .